The diesel engine (can be equipped with a clutch) is combined with the fire pump through a highly elastic coupling to form a fire pump unit. The unit also includes diesel tanks, cooling water tanks, fans, control panels (for automatic units) and other components.
When the unit is automatically controlled, the split or diesel engine automatic control cabinet (programmable) realizes the automatic start, input, and automatic switching of the system (switching from the electric pump group to the diesel engine pump group or from this group of diesel engine pump groups to another group of diesel engines) pump set), automatic protection (diesel engine overspeed, low oil pressure, high water temperature, three start failures, low oil level, low battery voltage and other alarm shutdown protection) and other functions, and can also interface with the user’s fire center or automatic fire alarm device, Realize remote monitoring.