The diesel engine mobile pump truck is an intelligent control product, and the operation information is displayed in informational information. The running status display of the diesel engine mobile pump truck includes: waiting, starting, fuel supply, starting, starting delay, idling delay, normal operation, cooling shutdown, emergency shutdown. The display of equipment operating parameters includes: water pump speed, water pump head, cooling temperature, lubricating oil pressure, water pump flow, running time, fuel stock, starting battery voltage and other parameters. Equipment protection settings include: overspeed, low speed, low oil pressure, high cooling temperature, low air temperature (less than 4°C), low fuel level, low battery voltage, high battery voltage, uncalibrated speed signal, and water pump water pressure is too low and over Flow and other pre-alarms; no speed signal, overspeed, low speed, low oil pressure, high cooling temperature, start failure, shutdown failure, oil pressure sensor open/short circuit, water temperature sensor open/short circuit, speed sensor open/short circuit, water pump water pressure over Automatic alarm for low and over flow;