24 hours Hotline: 0086-570-3010111
Free Call
PRODUCTS
EDJ Fire pump set

EDJ Fire pump set

Flow:
30-9000 GPM
Head:
3-20Bar
power:
Diesel /Electric Pump:1.5-710kw; Jockey Pump:0.55-160kw
Caliber:
25-800mm
Speed:
740-2900 r/min
Material:
HT200 , SS304,Bronze
Share:
Product Overview
Structure
Application
Technical Data
Inquiry
Product Overview
Fire pump set manufactured by Better Technology CO., LTD. In accordance with the Chinese national standard GB27898.5-2011 fixed fire water supply equipment part 5 "fire double power water supply equipment" hereinafter referred to as “packaged fire pump”, “ Fire Pump Set” or “fire pump packages” and National Fire Protection Association's NFPA20 "Standard for the Installation of Stationary Pumps for Fire Protection"(2016). and meet the latest Chinese national standard CCCF certification requirements and obtain a certificate. Fire pump package is one of the reliable products in fire water supply equipment.

Types of pumps used for fire service include: End Suction Pump,  Split Case Pump, Vertical Inline Pump and Vertical Turbine Pump.

1. Electric motor driven pump, can use single stage pump, horizontal split case pump, end suction pump,multistage pump.
2.Diesel engine pump, with capacity and head equal to electric pump, with fuel tank, water tank, fan,control box.
3. Jockey pump, horizontal or vertical, capacity will be small, but head should be higher than electric anddiesel engine pump.
4. Control panel: Auto Control of electric pump, diesel engine pump and Jockey Pump with overload, overcurrent protection.

Whether you are part of a fire department, an industrial facility, a construction site, or a rural area, the EDJ Diesel Engine Fire Pump System is an indispensable firefighting asset. Count on the EDJ Fire Pump System to provide reliable support and swift containment of fires!
Structure
 
Application
Fire pumps are essential safety equipment utilized in various application environments to ensure an adequate water supply for controlling fires and safeguarding lives and property. These environments include:

1.Buildings and High-Rise Structures: Fire pumps are crucial for ensuring adequate water pressure and flow in emergency situations, especially in large commercial and residential buildings.

2.Industrial Facilities: Factories, manufacturing plants, and chemical facilities rely on robust fire pump systems to protect equipment, materials, and personnel from fire hazards.

3.Oil Fields and Petrochemical Plants: Fire pumps play a critical role in addressing fires caused by oil and chemical spills in oil fields, refineries, and chemical plants.

4.Transportation Hubs: Airports, ports, train stations, and public transit centers require fire pumps to ensure the safety of a large number of people and protect critical infrastructure.

5.Energy Production: Power plants, nuclear facilities, and renewable energy installations use fire pumps to safeguard power generation equipment and energy supplies.

6.Specialized Environments: Certain applications may involve hazardous gases, explosion risks, or unique challenges, necessitating specially designed fire pumps to adapt to these conditions.

7.Maritime and Shipping: Ships, oil tankers, and offshore platforms rely on fire pumps to handle fires that may occur at sea.
Technical Data
100GPM @4BAR
Pump Model Capacity(GPM)

 

Head(BAR)

 

Power(KW)

 

Material
Electric XBD4/5-50L(50-200)

 

100 4 5.5 cast iron
Diesel engine XBC4/5-IS 100 4 5.5 cast iron
Jockey CDL2-70 10 5 0.75 SS304
100GPM @6BAR
Pump Model Capacity(GPM)

 

Head(BAR)

 

Power(KW)

 

Material
Electric XBD6/5-65L(65-250B)

 

100 6 7.5 cast iron
Diesel engine XBC6/5-IS 100 6 7.5 cast iron
Jockey CDL2-100 10 7 1.1 SS304
200GPM @6BAR
Pump Model Capacity(GPM)

 

Head(BAR)

 

Power(KW)

 

Material
Electric XBD6/10-65L(65-250)

 

200 6 15 cast iron
Diesel engine XBC4/5-IS 200 6 22 cast iron
Jockey CDL4-90 20 7 2.2 SS304
500GPM @5BAR
Pump Model Capacity(GPM)

 

Head(BAR)

 

Power(KW)

 

Material
Electric XBD5/30-100L(100-200)

 

500 5 22 cast iron
Diesel engine XBC5/30-IS 500 5 30 cast iron
Jockey CDL12-60 50 6 4 SS304
500GPM @8BAR
Pump Model Capacity(GPM)

 

Head(BAR)

 

Power(KW)

 

Material
Electric XBD8/30-100L(100-250)

 

500 8 37 cast iron
Diesel engine XBC8/30-D 500 8 45 cast iron
Jockey CDL12-90 50 9 5.5 SS304
500GPM @10BAR
Pump Model Capacity(GPM)

 

Head(BAR)

 

Power(KW)

 

Material
Electric XBD10/30-100L(100-315A)

 

500 10 55 cast iron
Diesel engine XBC10/30-D 500 10 55 cast iron
Jockey CDL12-110 50 11 7.5 SS304
750GPM @9BAR
Pump Model Capacity(GPM)

 

Head(BAR)

 

Power(KW)

 

Material
Electric XBD9/50-125L(125-250)

 

750 9 55 cast iron
Diesel engine XBC9/50-D 750 9 90 cast iron
Jockey CDL16-90 70 10 11 SS304
750GPM @10BAR
Pump Model Capacity(GPM)

 

Head(BAR)

 

Power(KW)

 

Material
Electric XBD10/50-150L(150-315A)

 

750 10 90 cast iron
Diesel engine XBC10/50-D 750 10 90 cast iron
Jockey CDL16-100 70 11 11 SS304
more specification, please contact us
Inquiry
If you have any question or comment, please contact us without hesitation. We will reply you as soon as possible.( * is required information)
* Your email:
* Your name:
* Country:
* Company Name:
Tel:
Contact address:
* Message:
RELATED PRODUCTS
UL ISO EDJ Fire Pump Set
UL ISO EDJ Fire Pump Set
Flow:
30-9000 GPM
Head:
3-20 bar
Speed:
740-2900 r/min
End Suction EEDJ Fire Pump Set
End Suction EEDJ Fire Pump Set
Flow:
30-9000 GPM
Head:
3-20 Bar
Speed:
740-2900 r/min
Multistage EDJ Fire Pump Set
Multistage EDJ Fire Pump Set
Flow:
30-9000 GPM
Head:
3-20 Bar
Caliber:
25-800 mm